Dyme Metals

DM Class 2000

FL# 47754.4

2” Mechanical Seam (18” Wide)

24ga and 22ga Galvalume

Approved

DM 2000

Approved for installation outside of the HVHZ (Miami-Dade & Broward counties)

material

Panel Material

24ga Galvalume (min) Corrosion resistant per FBC 1507.4.3 (non-HVHZ).

panel description

Panel Description

Non-Structural steel roof panel with 2” tall rib (nominal) and 18” (max) coverage.

deck

Deck/Substrate

2x4 P.T. Wood Battens (min) spaced 24” max. O.C. over a solid wood deck and fastened to 2x (min) wood roof joists spaced 24” max O.C. with (2) #8x3” FH wood screws.

options

Available Options

22ga galvalume also available and acceptable. 16”, 14”, and 12” widths also available and acceptable.

Installation​

*Be sure to review the installation notes included in the Evaluation Report document.

This product is approved for installation outside the HVHZ (Miami-Dade & Broward counties). References to HVHZ sections of the FBC (e.g. Fire Barrier) generally do not apply when the product is installed outside of the HVHZ.

Underlayment​

Comply with FBC 1507.1.1 (non-HVHZ), and per local codes.

Slope

Comply with FBC 1507.4.2 (non-HVHZ), and per local codes. OUTSIDE the HVHZ, FBC 1507.4.2 minimum slope is 1/4:12.

Trim and Flashing Details

Comply with manufacturer’s recommendations and RAS 133.

Fire Barrier

Comply with FBC 1516.1 and 1516.2 where required. Where not required by code. Fire classification is not a part of this evaluation. Where required, refer to a current fire directory listing for fire ratings of this roofing system assembly as well as the location of the fire barrier within the assembly.

Panel Labeling

Products sold that require labeling shall bear the following or similar label. Other labeling in accordance with FBC 1523.5 shall also be permitted.

Technical Documentation

1) This product has been tested to meet the standards listed below by Intertek Testing (TST-152).

2) Per reports S9448.09-450-44 and S9448.16-450-18, signed and sealed by Tanya Dolby, PE, and by PRI Construction Materials Technologies, per test reports VLS-004-02-01 and VLS-005-02-01.

3) Drawing 2MSOWB, dated 9/5/25, signed and sealed by Scott Wolters, PE.

4) Supplemental Calculations to support 2MSOWB, signed & sealed by Scott Wolters, PE.

5) Reports used for evaluation are owned by Lara’s IP & Research, LLC., and used with prior written permission.

Reviewed per the FAC Product Approval Rule, Chapter 61G20-3.005 (4), this product, as described in this report and drawing 2MSOWB, meets all of the requirements of section 1504.3.2 (non-HVHZ) of the 8th Edition (2023) Florida Building Code. This product as described has been tested and demonstrated compliance with:

UL580 – Test for Uplift Resistance of Roof Assemblies
UL 1897 – Uplift test for roof covering systems
TAS 110 – Physical Properties of Roofing Components
FM 4471 – Section 4.4 Resistance to Foot Traffic

Compare the maximum allowable loads to the ASD uplift pressures for the project to determine sufficiency and installation requirements. Determine project uplift pressures using ASCE 7-22, FBC R301, project design documents, guidance from local building department, or other design professionals. Engineering analysis may be completed by other licensed engineers for project specific approval by local authorities having jurisdiction.

Design of deck and roof structure (to include attachment of plywood and battens) shall be completed by others. Fire classification and shear diaphragm design are outside the scope of this evaluation.

This report is limited to compliance with structural wind load requirements of FBC 1504.3.2, as required by Rule 61G20-3. Neither Wolters Engineering nor the manufacturer shall be responsible for any conclusions, interpretations, or designs made by others based on this evaluation report. This report is limited solely to documenting compliance with Rule 61G20-3 and makes no express or implied warranty regarding performance of this product. Installation shall be subject to the local building code and authority having jurisdiction.

Panels may be formed on the jobsite with the following DYME Metals Association, LLC approved machines, under a quality assurance program audited by an approved 3rd. party QA auditor

SSP-10751007, 5VC-0700123, SSQ2U-6470323, SSQ2U-6480323, SSQ-6800617, SSQ-6690517, 5VC-0490718, SSQ5150216, SSQ-4560615, 5VC-0360516, SSQ-6810617, SSQ2U-4031121, SSQ2U-4041121, SSQU-4051121